Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013
Appendix C EtherNet/IP Objects
Instances
The number of instances depends on the number of parameters in the DPI drive.
The adapter parameters are appended to the list of drive parameters. The total
number of parameters can be read in Instance 0, Attribute 2.
Class Attributes
Instance
Description
0
Class Attributes
1
Drive Parameter 1 Attributes
…
…
n
Last Drive Parameter n Attributes
(1)
(1) n represents the number of parameters in the drive.
n + 1
Adapter Parameter 1 Attributes
…
…
n + m
Last Adapter Parameter m Attributes
(2)
(2) m represents the number of parameters in the adapter.
Attribute ID
Access Rule
Name
Data Type
Description
1
Get
Revision
WORD
1
2
Get
Max Instance
WORD
Number of parameters
8
Get
Parameter Class Descriptor
WORD
0 = False, 1 = True
Bit 0 = Supports parameter instances
Bit 1 = Supports full attributes
Bit 2 = Must do NVS save command
Bit 3 = Parameters are stored in NVS
9
Get
Configuration Assembly Instance
WORD
0
10
Set
Native Language
BYTE
0 = English
1 = French
2 = Spanish
3 = Italian
4 = German
5 = Japanese
6 = Portuguese
7 = Mandarin Chinese
8 = Russian
9 = Dutch