Table 2, Table 3, Table 4 – Rockwell Automation 20-COMM-ER 20-COMM-ER Dual-Port EtherNet/IP Communication Adapter User Manual User Manual

Page 64

Advertising
background image

64

Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013

Chapter 4 Configuring the I/O

Table 2 - Devices with 16-bit Reference/Feedback and 16-bit Datalinks

These products include the following:

Table 3 - Devices with 16-bit Reference/Feedback and 32-bit Datalinks

These products include the following:

Table 4 - Drives with 32-bit Reference/Feedback and 32-bit Datalinks

These products include the following:

·

PowerFlex 70 drives with standard or enhanced control

·

SMC Flex smart motor controllers

·

PowerFlex 700 drives with standard control

·

SMC-50 smart motor controllers

·

PowerFlex 700H drives

Logic

Command/

Status

Ref/Fdbk

(16-bit)

Datalinks (16-bit) User Configured Settings

A

B

C

D

Size in Words

Par. 23 -

[DPI I/O Cfg]

Par. 35 -

[M-S Input]

Par. 36 -

[M-S Output]

Input Output

4

2

…0 0001

…0 0001

…0 0001

6

4

…0 0011

…0 0011

…0 0011

8

6

…0 0111

…0 0111

…0 0111

10

8

…0 1111

…0 1111

…0 1111

12

10

…1 1111

…1 1111

…1 1111

·

PowerFlex 700 drives with vector control

·

PowerFlex Digital DC drives

·

PowerFlex 700L drives with 700 control

·

SMC Controllers

Logic

Command/

Status

Ref/Fdbk

(16-bit)

Datalinks (32-bit) User Configured Settings

A

B C

D

Size in Words

Par. 23 -

[DPI I/O Cfg]

Par. 35 -

[M-S Input]

Par. 36 -

[M-S Output]

Input Output

4

2

…0 0001

…0 0001

…0 0001

8

6

…0 0011

…0 0011

…0 0011

12

10

…0 0111

…0 0111

…0 0111

16

14

…0 1111

…0 1111

…0 1111

20

18

…1 1111

…1 1111

…1 1111

·

PowerFlex 700S drives with Phase I or Phase II control

·

PowerFlex 753 drives

·

PowerFlex 700L drives with 700S control

·

PowerFlex 755 drives

Logic

Command/

Status

Ref/Fdbk

(32-bit)

Datalinks (32-bit) User Configured Settings

A

B

C

D

Size in Words

Par. 23 -

[DPI I/O Cfg]

Par. 35 -

[M-S Input]

Par. 36 -

[M-S Output]

Input Output

6

4

…0 0001

…0 0001

…0 0001

10

8

…0 0011

…0 0011

…0 0011

14

12

…0 0111

…0 0111

…0 0111

18

16

…0 1111

…0 1111

…0 1111

22

20

…1 1111

…1 1111

…1 1111

TIP

For instructions on configuring the I/O for the adapter using Parameter 25 -

[DPI I/O Cfg] and its Master-Slave Hierarchy using Parameters 37 - [M-S

Input] and 38 - [M-S Output], see

Setting the I/O Configuration on page 35

.

Advertising