Chapter 4 Configuring the I/O

1.

In the treeview, right-click on the bridge and choose New Module… to
display the Select Module screen.

In our example, we right-click on the 1756-ENBT/A bridge. Expand the
Drives group to display all of the available drives with their
communication adapters.

2.

From the list, select the drive and its connected adapter.

For this example, we selected ‘PowerFlex 70 EC-E’.

3.

Click OK.

The drive’s New Module screen appears.

4.

On the General tab, edit the following data about the drive/adapter.

5.

On the New Module screen in the Module Definition section, click
Change…

to launch the Module Definition screen and begin the drive/

adapter configuration process.

In this example, Datalinks are used to do the following.

TIP

If the PowerFlex drive is not shown, go to

www.ab.com/support/abdrives/

webupdate

and download the latest RSLogix 5000 device Add-on Profile.

BoxSetting
Name

A name to identify the drive.

Description

Optional – description of the drive/adapter.

IP Address

The IP address of the adapter.

Read…

Write to…

Output Current (Parameter 3)

Accel Time 1 (Parameter 140)

DC Bus Voltage (Parameter 12)

Decel Time 1 (Parameter 142)

Fault 1 Code (Parameter 243)

High Resolution Reference (Parameter 308)

TIP

To get the latest RSLogix 5000 device Add-on Profile, go to

www.ab.com/support/abdrives/webupdate

.