Selecting master-slave or peer-to-peer, Setting a master-slave hierarchy 36, Setting a master-slave hierarchy (scanner-to-drive – Rockwell Automation 20-COMM-ER 20-COMM-ER Dual-Port EtherNet/IP Communication Adapter User Manual User Manual

Page 36: Selecting master-slave or peer-to, Peer

Advertising
background image

36

Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013

Chapter 3 Configuring the Adapter

Selecting Master-Slave or

Peer-to-Peer

A hierarchy determines the type of device with which the adapter exchanges data.
In a Master-Slave hierarchy, the adapter exchanges data with a master, such as a
scanner or bridge (1756-ENBT, 1756-EN2T, 1747-L5-xxx, and so forth). In a
Peer-to-Peer hierarchy, the adapter exchanges data with one or more EtherNet/IP
adapters in other devices. (The devices must have compatible Logic Command/
Status words.)

For both Master-Slave and Peer-to-Peer hierarchies, the devices exchanging data
must be on the same IP subnet. See ‘IP Addresses’ in the for information about
IP subnets.

Setting a Master-Slave Hierarchy (Scanner-to-Drive

Communication)

1.

Enable the desired I/O in Parameter 25 - [DPI I/O Cfg].

See

Setting the I/O Configuration on page 35

.

2.

Set the bits in Parameter 37 - [M-S Input].

This parameter determines the data received from the master by the
device. A ‘1’ enables the I/O and a ‘0’ disables the I/O.

Bit 0 is the right-most bit. It is highlighted above and equals ‘1’.

3.

Set the bits in Parameter 38 - [M-S Output].

This parameter determines the data transmitted from the device to the
scanner. A ‘1’ enables the I/O and a ‘0’ disables the I/O.

Bit 0 is the right-most bit. It is highlighted above and equals ‘1’.

4.

Reset the adapter; see

Resetting the Adapter on page 43

.

Bit

Description

0

Logic Command/Reference (Default)

1

Datalink A Input

2

Datalink B Input

3

Datalink C Input

4

Datalink D Input

5…15 Not Used

Port 5 Device
20-COMM-ER
Parameter #: 37

M-S Input

x x x x x x x x x x x 0 0 0 0

1

Cmd/Ref

b00

Bit

Description

0

Status/Feedback (Default)

1

Datalink A Output

2

Datalink B Output

3

Datalink C Output

4

Datalink D Output

5…15 Not Used

Port 5 Device
20-COMM-ER
Parameter #: 38

M-S Output

x x x x x x x x x x x 0 0 0 0

1

Status/Fdbk

b00