Using Explicit Messaging Chapter 6

ControlLogix Controller – Formatting a Message to Read a Single Parameter,

RSLogix 5000 Software, Version 15.00 or Later

Figure 36 - Parameter Read Single Message Configuration Screens

The following table identifies the data that is required in each box to configure a
message to read a single parameter.

Configuration Tab

Example Value

Description

Message Type

Service Type

(1)

Service Code

(1)

Class

Instance

(2)

Attribute

Destination

CIP Generic

Parameter Read

e (Hex.)

f (Hex.)

3 (Dec.)

1 (Hex.)

Output_Current

(4)

Used to access the Parameter Object in the adapter.

This service is used to read a parameter value.

Code for the requested service.

Class ID for the DPI Parameter Object.

Instance number is the same as parameter number.

Attribute number for the Parameter Value attribute.

The tag where the data that is read is stored.

Communication Tab

Example Value

Description

Path

(3)

My_PowerFlex_Drive

The path is the route that the message will follow.

Tag Tab

Example Value

Description

Name

Single_Read_Message The name for the message.

(1) The default setting for Service Type is ‘Custom’, enabling entry of a Service Code not available from the Service Type pull-

down menu. When choosing a Service Type other than ‘Custom’ from the pull-down menu, an appropriate Hex. value is
automatically assigned to the Service Code box which is dimmed (unavailable).

(2) Only drive parameters (Port 0) can be read using Parameter Object Class code 0x0F. To read a parameter of a peripheral in

another port, use DPI Parameter Object Class code 0x93 (see

page 121

).

(3) Click Browse to find the path, or type in the name of the device listed in the I/O Configuration folder.

(4) In this example, Output Current is a 32-bit parameter requiring the Data Type field to be set to ‘DINT’ when creating the

controller tag. If the parameter being read is a 16-bit parameter, the tag Data Type field must be set to ‘INT’. When using a
PowerFlex 700S drive, Output Current is a floating point parameter requiring the Data Type field to be set to ‘REAL’ when
creating the controller tag. See the drive documentation to determine the size of the parameter and its data type (16-bit or
32-bit integer or REAL).