Chapter 6 Using Explicit Messaging

ControlLogix Controller Example Ladder Logic Program to Write a Single

Parameter, RSLogix 5000 Software, Version 15.00 or Later

A Parameter Write message is used to write to a single parameter. This write
message example writes a value to parameter 140 - [Accel Time 1] in a PowerFlex
7-Class drive.

Table 19 - Example Controller Tags to Write a Single Parameter

Figure 37 - Example Ladder Logic to Write a Single Parameter

Important: If the explicit message single write must be written

continuously, use DPI Parameter Object Class code 0x93. This
writes to RAM—not NVS (EEPROM) memory. This example
single write message using Class code F writes to NVS. Over
time, continuous writes will exceed the EEPROM life cycle and
cause the drive to malfunction.

ControlLogix Controller – Formatting a Message to Write a Single Parameter,

RSLogix 5000 Software, Version 15.00 or Later

Figure 38 - Parameter Write Single Message Configuration Screens

Operand

Controller Tags for Single Write Message

Data Type

XIC

Execute_Single_Write_Message

BOOL

MSG

Single_Write_Message

MESSAGE