Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013

69

Configuring the I/O Chapter 4

Figure 12 - Example MicroLogix 1100/1400 Controller EtherNet/IP Network

Configuring Parameters for Network I/O

Because the I/O for the drive is message-based, there is no need to configure any
I/O inside the RSLogix 500 project, version 7.00 or later, until using the I/O as
described in

Chapter 5

.

However, to get the adapter to operate with the I/O created in

Chapter 5

, we

need to configure the adapter to accept the I/O and drive to point to the
appropriate Datalinks.

1.

For this example, the following adapter I/O parameters are set to the
following values.

2.

Reset the adapter (see

Resetting the Adapter on page 43

) or power cycle

the drive.

For the drive speed reference and Datalink parameter values and the
adapter setup parameter values, refer to

Drive and Adapter Parameter

Settings on page 96

.

IP Address 10.91.100.81
MicroLogix 1100/1400 Controller

IP Address 10.91.100.79
PowerFlex 70 Drive with
20-COMM-ER Adapter

Computer with
Ethernet Connection

Ethernet
Switch

TIP

Information for PowerFlex 750-Series drives has been added where applicable.

Adapter Parameter No.

Setting

25 - [DPI I/O Cfg]

xxxx xxxx xxx1 1111

37 - [M-S Input]

xxxx xxxx xxx1 1111

38 - [M-S Output]

xxxx xxxx xxx1 1111