Rockwell Automation 20-COMM-ER 20-COMM-ER Dual-Port EtherNet/IP Communication Adapter User Manual User Manual

Page 132

Advertising
background image

132

Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013

Chapter 6 Using Explicit Messaging

MicroLogix 1100/1400 Controller Example Get Attribute Single Response

Data

In this message example, we use the data table address in

Figure 63

to store the

response value (0.13 amps) that was read from drive parameter 003 - [Output
Current]. To determine the data type for the parameter and its required scaling,
see the specific drive documentation.

Figure 63 - Example Get Attribute Single Response Data File

Figure 64

shows example ladder logic to correctly format the three possible data

types for read messages in the MicroLogix 1100/1400 controller.

Figure 64 - Example Ladder Logic to Format Parameter Data Types for Gets

For 16-bit Integer
Parameters – All
PowerFlex 7-Class
Drives

For 32-bit Integer
Parameters – All
PowerFlex 7-Class
Drives

For 32-bit REAL
(Floating Point)
Parameters –
PowerFlex 700S
and PowerFlex 750-
Series Drives

Advertising