Rockwell Automation 20-COMM-ER 20-COMM-ER Dual-Port EtherNet/IP Communication Adapter User Manual User Manual
Page 71

Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013
71
Configuring the I/O Chapter 4
Create MicroLogix 1100/1400 Ladder Logic for the Control Timeout
1.
In the RSLogix 500 project window treeview under Program Files double-
click on LAD 2.
2.
Insert a ladder rung.
3.
Double-click on the rung to display the rung editor.
4.
Enter MSG MGxx:n, where:
xx is an unused data file number (for example, MG10:n), and
n is an unused element of the data file chosen for xx (for example, MG10:0)
5.
Press Enter.
6.
Insert another separate rung.
7.
Double-click on the rung to display the rung editor.
8.
Enter BST XIC MGxx:n/DN NXB XIC MGxx:n/ER BND OTU
MGxx:n/EN
, where:
xx and n must correspond to the assigned data file number and element
(for example, MG10:0) for the message created in steps 2…5.
Important: The information must be entered with appropriate numbers
for ‘xx’ and ‘n’ for your application, and with spaces and
forward slashes exactly as shown.
9.
Press Enter.
10.
In the MSG instruction (
), double-click Setup Screen to launch
the message configuration screen (
).
Figure 13 - MicroLogix 1100/1400 Ladder Logic for the Control Timeout
11.
Configure the General tab fields by entering or verifying the information
shown in the message configuration screen.
Steps 2…5
Steps 6…9
Step 10