Viewing and clearing events, Using the him to view and clear events – Rockwell Automation 20-COMM-ER 20-COMM-ER Dual-Port EtherNet/IP Communication Adapter User Manual User Manual

Page 149

Advertising
background image

Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013

149

Troubleshooting Chapter 7

Viewing and Clearing

Events

The adapter has an event queue to record significant events that occur in the
operation of the adapter. When such an event occurs, an entry is put into the
event queue. You can view the event queue with any of these drive configuration
tools:

• LCD PowerFlex 7-Class HIM
• Connected Components Workbench software, version 1.02 or later
• DriveExplorer software, version 2.01 or later
• DriveExecutive software, version 1.01 or later
• Other clients using the DPI Fault object

The event queue can contain up to 32 entries. Eventually the event queue will
become full, since its contents are retained through adapter resets. At that point, a
new entry replaces the oldest entry. Only an event queue clear operation or
adapter power cycle will clear the event queue contents.

Resetting the adapter to defaults has no effect on the event queue.

Using the HIM to View and Clear Events

Step

Example Screen

Viewing Events

1. Access parameters in the adapter. See

Using the PowerFlex 7-

Class HIM on page 28

.

2. Press the

or

key to scroll to Diagnostics.

3. Press the

(Enter) key to display the Diagnostics menu in the

adapter.

4. Repeat steps 2 and 3 to enter the Events option and then View

Event Queue option.

5. Press the

or

key to scroll through events. The most

recent event is Event 1.

Clearing Events

1. Access parameters in the adapter. See

Using the PowerFlex 7-

Class HIM on page 28

.

2. Press the

or

key to scroll to Diagnostics.

3. Press the

(Enter) key to display the Diagnostics menu in the

adapter.

4. Repeat steps 2 and 3 to enter the Events option and then the

Clear Event option or Clr Event Queue option. A message will

pop up to confirm that you want to clear the message or queue.

5. Press the

(Enter) key to confirm your request. If Clr Event

Queue was selected, all event queue entries will then display ‘No

Event’.

Main Menu:

Diagnostics

Parameter

Device Select

Event Q:

1

E3

Ping Time Flt

Dgn: Events

View Event Queue

Clear Event

Clr Event Queue

Advertising