Using the him to view adapter diagnostic items – Rockwell Automation 20-COMM-ER 20-COMM-ER Dual-Port EtherNet/IP Communication Adapter User Manual User Manual

Page 147

Advertising
background image

Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013

147

Troubleshooting Chapter 7

Using the HIM to View Adapter Diagnostic Items

Table 24 - Adapter Diagnostic Items

Step

Example Screen

1. Access parameters in the adapter. See

Using the PowerFlex 7-

Class HIM on page 28

.

2. Press the

or

key to scroll to Diagnostics.

3. Press the

(Enter) key to display the Diagnostics menu in the

adapter.

4. Repeat steps 2 and 3 to enter the Device Items option.

5. Press the

or

key to scroll through the items.

Main Menu:

Diagnostics

Parameter

Device Select

Device Item #

3

Reference

No. Name

Description

1

Common Logic Cmd

The present value of the Common Logic Command being transmitted to the drive by this adapter.

2

Prod Logic Cmd

The present value of the Product Logic Command being transmitted to the drive by this adapter from the controller.

3

Reference

The present value of the Reference being transmitted to the drive by this adapter. Note that a 16-bit value will be

sent as the Most Significant Word of the 32-bit field.

4

Common Logic Sts

The present value of the Common Logic Status being received from the drive by this adapter.

5

Prod Logic Sts

The present value of the Product Logic Status being received from the drive by this adapter to the controller.

6

Feedback

The present value of the Feedback being received from the drive by this adapter. Note that a 16-bit value will be

sent as the Most Significant Word of the 32-bit field.

7

Datalink A1 In

The present value of respective Datalink In being transmitted to the drive by this adapter. (If not using a Datalink,

this parameter should have a value of zero.)

8

Datalink A2 In

9

Datalink B1 In

10

Datalink B2 In

11

Datalink C1 In

12

Datalink C2 In

13

Datalink D1 In

14

Datalink D2 In

15

Datalink A1 Out

The present value of respective Datalink Out being received from the drive by this adapter. (If the drive indicates a

16-bit datalink size, the value appears in the least significant 16 bits of this diagnostic item, and the most significant

16 bits of this diagnostic item are zero.)

16

Datalink A2 Out

17

Datalink B1 Out

18

Datalink B2 Out

19

Datalink C1 Out

20

Datalink C2 Out

21

Datalink D1 Out

22

Datalink D2 Out

23

DPI Rx Errors

The present value of the DPI Receive error counter.

24

DPI Rx Error Max

The maximum value (since reset) of the DPI Receive error counter.

25

DPI Tx Errors

The present value of the DPI Transmit error counter.

26

DPI Tx Error Max

The maximum value (since reset) of the DPI Transmit error counter.

27

Boot Flash Count

Number of times the boot firmware in the adapter has been flash updated.

28

App Flash Count

Number of times the application firmware in the adapter has been flash updated.

29

M-S Input Size

Size of data transferred from the network to the drive.

30

M-S Output Size

Size of data transferred from the drive to the network.