Connecting the adapter to the drive or smc – Rockwell Automation 20-COMM-ER 20-COMM-ER Dual-Port EtherNet/IP Communication Adapter User Manual User Manual

Page 20

Advertising
background image

20

Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013

Chapter 2 Installing the Adapter

Connecting the Adapter to

the Drive or SMC

1.

Remove ALL power from the drive or SMC.

2.

Use static control precautions.

3.

Remove the drive or SMC cover or open the drive door.

4.

Connect the Internal Interface cable to the DPI port on the drive and then
to the DPI connector on the adapter (see

Figure 3

).

5.

Secure and ground the adapter to the drive or SMC (see

Figure 4

) by doing

the following:
– On a PowerFlex 70 drive, fold the Internal Interface cable behind the

adapter and mount the adapter on the drive using the four captive
screws.

– On an SMC Flex, put the wire lug between the mounting screw and

20-COMM-ER board

Important:

Tighten all screws to properly ground the adapter.
Recommended torque is 0.9 N

•m (8.0 lb•in).

ATTENTION: Risk of injury or death exists. The PowerFlex drive or SMC
may contain high voltages that can cause injury or death. Remove ALL
power from the drive or SMC, and then verify power has been discharged
before installing or removing the adapter.