Rockwell Automation 20-COMM-ER 20-COMM-ER Dual-Port EtherNet/IP Communication Adapter User Manual User Manual

Page 128

Advertising
background image

128

Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013

Chapter 6 Using Explicit Messaging

MicroLogix 1100/1400 Controller Example Ladder Logic Program to Write a

Single Parameter Using Read/Write Parameter Service

A Write Parameter message is used to write to a single parameter. This write
message example writes a value to parameter 140 - [Accel Time 1] in a PowerFlex
7-Class drive.

Figure 57 - Example Ladder Logic to Write a Single Parameter

Important: If the explicit message single write must be written

continuously, use DPI Parameter Object Class code 0x93 and
attribute A (10 decimal; see

page 133

). This writes to RAM—

not NVS (EEPROM) memory. This example single write
message using Class code F writes to NVS. Over time,
continuous writes will exceed the EEPROM life cycle and
cause the drive to malfunction.

MicroLogix 1100/1400 Controller – Formatting a Message to Write a Single

Parameter Using Read/Write Parameter Service

Figure 58 - Write Parameter Message Configuration Screens

Advertising