Adapter Parameters Appendix B

51

52

[Peer A Output]

[Peer B Output]
Selects the source of the peer I/O output data. The

adapter transmits this data to the network.
Important: Changes to these parameters are

ignored when Parameter 53 - [Peer Out Enable]

is set to ‘1’ (On).

Default:

0 = Off

Default:

0 = Off

Values:

0 = Off

1 = Cmd/Ref

2 = Datalink A Input

3 = Datalink B Input

4 = Datalink C Input

5 = Datalink D Input

6 = Datalink A Output

7 = Datalink B Output

8 = Datalink C Output

9 = Datalink D Output

Type:

Read/Write

Reset Required: No

53

[Peer Out Enable]
Determines if peer I/O output is on or off.

Default:

0 = Off

Values:

0 = Off

1 = On

Type:

Read/Write

Reset Required: No

54

[Peer Out Time]
Sets the minimum time that an adapter will wait

when transmitting data to a peer.
Important: Changes to these parameters are

ignored when Parameter 53 - [Peer Out Enable]

is set to ‘1’ (On).

Default:

10.00 Seconds

Minimum:

0.01 Seconds

Maximum:

10.00 Seconds

Type:

Read/Write

Reset Required: No

55

[Peer Out Skip]
Sets the maximum time that an adapter will wait

when transmitting data to a peer. The value of

Parameter 54 - [Peer Out Time] is multiplied by

the value of this parameter to set the time.
Important: Changes to these parameters are

ignored when Parameter 53 - [Peer Out Enable]

is set to ‘1’ (On).

Default:

1

Minimum:

1

Maximum:

16

Type:

Read/Write

Reset Required: No

56

[Web Enable]
Displays the setting of the adapter Web Pages

Switch (SW2) when the adapter was last reset.

Default:

0 = Disabled

Values:

0 = Disabled

1 = Enabled

Type:

Read Only

57

[Web Features]
Sets the access to the Web interface and Web

configurable email notification feature.

Default:

xxxx xxx0

Bit Values:

0 = Disabled

1 = Enabled

Type:

Read/Write

Reset Required: No

Parameter
No. Name and Description

Details

Bit

Definition

Not

Used

Not

Used

Not

Used

Not

Used

Not

Used

Not

Used

Not

Used

E-m

ail

Cfg

Default

x

x

x

x

x

x

x

1

Bit

7 6 5 4 3 2 1 0