106

Rockwell Automation Publication 2094-UM003A-EN-P - May 2012

Appendix A

Using the Safe Torque-off Feature with the Kinetix 6000M System

Figure 40

demonstrates when the safe torque-off mismatch is detected and a

DriveHardFault is posted.

Figure 40 - System Operation in the Event that the Safety Enable Inputs Mismatch

When one safety input is turned off, the second input must also be turned off,
otherwise a fault is asserted (see

Figure 41

). The fault is asserted even if the first

safety input is turned on again.

Figure 41 - System Operation in the Event that the Safety Enable Inputs Mismatch Momentarily

ATTENTION: The safe torque-off fault (E49) is detected upon demand of the
safe torque-off function. After troubleshooting, a safety function must be
executed to verify correct operation.

IMPORTANT

The Safe Torque Off fault (E49) can be reset only if both inputs are in the Off-
state for more than 1 second. After the E49 reset requirement is satisfied, an
MASR command in RSLogix software should be issued to reset the
DriveHardFault.

SAFETY ENABLE1+

24V DC

24V DC

0V DC

0V DC

1

1

0

0

SAFETY ENABLE2+

DriveHardFault

SafeOffModeActiveStatus

1 Second

SAFETY ENABLE1+

24V DC

24V DC

0V DC

0V DC

1

1

0

0

SAFETY ENABLE2+

DriveHardFault

SafeOffModeActiveStatus

1 Second