Connecting the Kinetix 6000M System
Chapter 5
Signal integrity is very important for successful operation of an integrated drive-
motor system. You must be sure that all cables are properly grounded through the
IPIM module to the ground plane of the Kinetix drive system.
• Verify that every cable shield directly connects to chassis ground.
• Clamp the exposed section of the hybrid cable shield in the cable (chassis)
ground connection on the drive. Refer to
.
Figure 21 - Hybrid Cable Shields
Apply the Cable Shield Clamp
The cable shield clamp assures a solid bond to the shield and secures the cable.
1. Depress the spring loaded clamp.
2. Position the exposed portion of the cable braid directly in line with the
clamp.
3. Release the spring, making sure the cable and cable braid are held secure by
the clamp.