Ipim module fault diagnosis – Rockwell Automation MDF-SB1304F Kinetix 6000M Integrated Drive-Motor System User Manual

Page 93

Advertising
background image

Rockwell Automation Publication 2094-UM003A-EN-P - May 2012

93

Troubleshooting the Kinetix 6000M System

Chapter 7

IPIM Module Fault Diagnosis

When a fault condition is detected, it is added to a fault log, opens the power rail
SYSOK and reports the fault to the IAM module. This causes a loss of bus power
to all modules on the Bulletin 2094 power rail and associated IDM units. If an
IPIM module fault is detected, the fault will be displayed on the IPIM module.
In addition, the IPIM module will display IDM unit faults.

The IAM module generates a fault whenever an IPIM module fault occurs,
regardless of the state of the contactor. IDM unit faults are not displayed by the
IAM module.

Issuing a fault reset command to the IAM module will also send a fault reset
command to the IPIM module.

The IPIM module maintains a log of the last 50 faults reported by the IPIM
module or any of the connected IDM units. Each fault contains the source of the
fault (IDM unit number or IPIM module), the fault number, and a timestamp
with the cumulative power-on time of the IPIM module.

No rotation

The IDM unit connections are loose or
open.

Check IDM unit wiring and connections.

Foreign matter is lodged in the IDM unit.

Remove foreign matter.

The IDM unit load is excessive.

Verify the servo system sizing.

The bearings are worn.

Return the IDM unit for repair.

The IDM unit brake is engaged (if
supplied).

Check brake wiring and function.
Return the IDM unit for repair.

The IDM unit is not connect to the load.

Check coupling.

IDM unit overheating

The duty cycle is excessive.

Change the command profile to reduce accel/
decel or increase time.

The rotor is partially demagnetized
causing excessive IDM unit current.

Return the IDM unit for repair.

Abnormal noise

IDM unit tuning limits are set too high.

Run Tune in RSLogix 5000 software.

Loose parts are present in the IDM unit.

Remove the loose parts.
Return IDM unit for repair.
Replace IDM unit.

Through bolts or coupling is loose.

Tighten bolts.

The bearings are worn.

Return IDM unit for repair.

Mechanical resonance.

Notch filter may be required (refer to Axis
Properties dialog box, Output tab in
RSLogix 5000 software).

Condition

Potential Cause

Possible Solution