Kinetix 6000M System Connector Data

Chapter 4

Sercos Fiber-optic Connectors

The sercos fiber-optic ring is connected by using
the sercos receive (RX) and transmit (TX)
connectors.

Table 12 - Sercos Specifications

Enable Input

One digital input is supplied to enable all connected IDM units.
The enable status is transmitted to all of the IDM units.

Table 13 - Enable Input Specifications

ATTENTION: To avoid damage to the sercos RX and TX connectors use only
finger-tight torque when attaching the fiber-optic cables. Do not use a wrench
or any other mechanical assistance. For more information, refer to Fiber-optic
Cable Installation and Handling Instructions, publication

2090-IN010

.

Attribute

Value

Data rates

8 Mbps (fixed)

Light intensity

Adjustable, low or high power, selectable via the keypad/LCD display (see

page 68

).

Cyclic update period

500 μs, minimum

Node addresses

Assigned on each IDM unit, see

page 70

. The IPIM module does not have a sercos address

since it is not a sercos device.

Terminal

Description

Signal

Strip
Length
mm (in.)

Torque
N•m (lb•in)

Min/Max
Wire Size

(1)

mm

2

(AWG)

(1) Maximum/minimum that the connector will accept—these are not recommendations.

1

+24V DC Enable Supply

ENABLE 24V+

+

7.0
(0.275)

0.235 (2.0)

0.14…1.5
(30…14)

2

Enable Input

ENABLE INPUT

EN

3

24V DC Common

ENABLE 24V COM

-

Signal

Description

IDM Unit
Reaction
Time

Edge/Level
Sensitive

ENABLE

Optically isolated, single-ended active high signal. Current loading is
nominally 10 mA. A 24V DC input is applied to this terminal to enable all
modules. The reaction time for all IDM units connected to the IPIM is 30 ms,
maximum.

30 ms

Level

Transmit

Receive

1

+

EN

-