Chapter 5

Connecting the Kinetix 6000M System

Figure 24 - Hybrid Cable Installed

Network Cable

The IDM system network is routed by using 2090-CNS

xPxS-AAxx cables. A

2090-CNSSPRS-AA

xx or 2090-CNSSPSS-AAxx cable is required for

connection to the IPIM module.

When installing network cables, torque the connector plug to 0.8…1.2 N•m
(7.1…10.6 lb•in) to fully seat the contacts and secure the connection.

How to Bypass an IDM Unit

A 2090-CCPPS8S coupler cable joins two hybrid cables to bypass an IDM unit
or extend the length of a cable. This can be desired when performing
maintenance on a unit or to simply extend a hybrid cable. IDM to IDM cable
lengths should not exceed 25 m (82.0 ft) during normal operation when a
coupling cable is used.

The IDM network cables can be joined to together without the need of a coupler
to bypass an IDM unit or extend network cables.


42+
42-
SH2
CN-
CN+
OUT
RTN
SH3
SE1
SE-
SE2


42+
42-
SH2
CN-
CN+
OUT
RTN
SH3
SE1
SE-
SE2

Hybrid Cable

Hybrid Cable Communication
Signals Connector

Hybrid Cable DC Bus Connector

2090-CNSSPRS-AAxx

2090-CNSSPSS-AAxx

2090-CNSRPSS-AAxx

(1)

2090-CNSRPRS-AAxx

(1)

(1) Not for connection to an IPIM module.