Network cable, How to bypass an idm unit – Rockwell Automation MDF-SB1304F Kinetix 6000M Integrated Drive-Motor System User Manual
Page 58

58
Rockwell Automation Publication 2094-UM003A-EN-P - May 2012
Chapter 5
Connecting the Kinetix 6000M System
Figure 24 - Hybrid Cable Installed
Network Cable
The IDM system network is routed by using 2090-CNS
xPxS-AAxx cables. A
2090-CNSSPRS-AA
xx or 2090-CNSSPSS-AAxx cable is required for
connection to the IPIM module.
When installing network cables, torque the connector plug to 0.8…1.2 N•m
(7.1…10.6 lb•in) to fully seat the contacts and secure the connection.
How to Bypass an IDM Unit
A 2090-CCPPS8S coupler cable joins two hybrid cables to bypass an IDM unit
or extend the length of a cable. This can be desired when performing
maintenance on a unit or to simply extend a hybrid cable. IDM to IDM cable
lengths should not exceed 25 m (82.0 ft) during normal operation when a
coupling cable is used.
The IDM network cables can be joined to together without the need of a coupler
to bypass an IDM unit or extend network cables.