Rockwell Automation Publication 2094-UM003A-EN-P - May 2012

115

Appendix

C

Upgrading the Kinetix 6000M System Firmware

This appendix provides procedures for upgrading firmware for the
Kinetix 6000M integrated drive-motor (IDM) units and IDM power interface
modules (IPIM).

Upgrading firmware for the Kinetix 6000M system is done by using
ControlFLASH software. The procedure for upgrading the IDM units uses the
sercos interface, similar to axis modules. However, upgrading firmware on the
IPIM module is accomplished over the EtherNet/IP network.

Before You Begin

You need the following software and information before you begin.

Topic

Page

Before You Begin

115

Configure Logix Communication

116

IPIM Module Firmware Upgrade

117

IDM Unit Firmware Upgrade

122

Verify the Firmware Upgrade

126

Description

Cat. No.

Firmware Revision or
Software Version

RSLogix 5000

software

9324-RLD300NE

20.01

(2)

or later

(2) Version 20.00 may be used if the motion database has been updated.

ControlLogix sercos module

1756-MxxSE

20.007 or later

CompactLogix sercos module

1768-M04SE

20.007 or later

SoftLogix sercos PCI card

1784-PM16SE

20.007 or later

RSLinx® software

2.59 or later

ControlFLASH software kit

(1)

(1) Download the ControlFLASH kit from

http://support.rockwellautomation.com/controlflash

. Contact Rockwell Automation Technical

Support at (440) 646-5800 for assistance.
For more ControlFLASH information (not drive specific), refer to the ControlFLASH Firmware Upgrade Kit Quick Start, publication

1756-QS105

.

From website

Catalog number of the targeted IPIM module and IDM unit you want to upgrade

Network path to the targeted IPIM module and IDM unit.

IMPORTANT

Control power must be present prior to upgrading your IPIM module or IDM
units.

ATTENTION: To avoid personal injury or damage to equipment during the
firmware upgrade due to unpredictable motor activity, do not apply 3-phase AC
or common-bus DC input power to the IAM module.