Idm unit fault diagnosis, Logix controller/idm unit fault behavior – Rockwell Automation MDF-SB1304F Kinetix 6000M Integrated Drive-Motor System User Manual
Page 95

Rockwell Automation Publication 2094-UM003A-EN-P - May 2012
95
Troubleshooting the Kinetix 6000M System
Chapter 7
IDM Unit Fault Diagnosis
Logix Controller/IDM Unit Fault Behavior
These RSLogix 5000 fault actions are configurable from the Axis Properties
dialog box, Fault Actions tab.
Table 21 - Fault Action Definitions
Only selected faults are programmable.
indicates which faults have a
programmable RSLogix Fault Action. Faults that do not have a programmable
fault action will have the Shutdown action described in
Figure 38 - RSLogix 5000 Axis Properties - Fault Actions Tab
Fault Action
Definition
Shutdown
Axis is disabled as defined in
. In addition, the axis in Logix enters the Shutdown
state, which disables any axes that are using this axis as a camming or gearing master. The
AxisHomedStatus tag for the faulted axis is cleared. Shutdown is the most severe action to a
fault and it is usually reserved for faults that could endanger the machine or operator if
power is not removed as quickly as possible.
Disable Drive
The axis is disabled as defined in the
Stop Motion
The axis decelerates at the maximum deceleration rate (set in RSLogix 5000 software>Axis
Properties>Dynamics tab). Once the axis has come to a stop, the servo loops remain enabled
but no further motion can be generated until the fault is reset. This is the gentlest stopping
mechanism in response to a fault. It is usually used for less severe faults.
Status Only
System continues to operate. Status is displayed on the IPIM module.
Drive Fault Action/Attribute for
IDM Overtemp fault (E04).
Table 22 - Exception/Fault Behavior
IPIM Display
(RSLogix Drive Fault)
IDM Status
Indicator
Potential Cause
Possible Solution
RSLogix
Programmable
Fault Action
Fault Behavior
E04 – Motor Overtemp
(MotorOvertempFault)
Flashing
Red
Excessive IDM unit temperature.
• Lower ambient temperature, increase IDM
unit cooling.
Yes
Decel/Disable
E05 – Power Fault
(DriveOvercurrentFault)
Flashing
Red
Operation above the IGBT
instantaneous current rating or IPIM
module power supply undervoltage.
• Operate within the instantaneous power
rating.
• Reduce acceleration rates.
• If fault persists, replace IDM unit.
No
Coast/Disable/
Open Contactor
Enable