Rockwell Automation Publication 2094-UM003A-EN-P - May 2012

57

Connecting the Kinetix 6000M System

Chapter 5

Figure 22 - IDM System Wiring

The colored rings on the hybrid cable connector and the mating cable must
match: red-to-red or green-to-green.

Hand-tighten the knurled collar on a hybrid cable approximately 45 degrees to
fully seat and lock the connector.

Wiring the Connectors

Use these guidelines as a reference when wiring the hybrid cable to the IPIM
module.

Figure 23 - 2090-CHBIFS8-12AAxx Hybrid Cable

1. Route the cable/wires to the module.
2. Insert wires into connector plugs.
3. Tighten the connector screws.

Refer to

page 39

for torque specifications.

4. Gently pull on each wire to make sure it does not come out of its terminal;

reinsert and tighten any loose wires.

5. Insert the connector plug into the module connector.

PORT 1

PORT 2

NETWORK

IDM to IDM Hybrid Cable

(2090-CHBP8S8-12AAxx)

IPIM Module

IDM Unit

IDM Unit

Network Terminator

Last IDM Unit

(2090-CTSRP)

Network Cable

(2090-CNSRPRS-AAxx)

Network Cable to First IDM

(2090-CNSSPRS-AAxx)

Hybrid Terminator

Last IDM Unit

(2090-CTHP8)

IPIM to IDM Hybrid Cable

(2090-CHBIFS8-12AAxx)

(Catalog numbers are in parenthesis.)

42- (white/blue)
42+ (blue)

CN- (white/brown)
CN+ (brown)
SH2 (drain)

RTN (pink)
OUT (white/pink)
SE1 (orange)
SE2 (yellow)
SE- (violet)
SH3 (drain)

DC+ (brown)
PE (green)
DC- (grey)

DC+

DC-

42-

42+

SH3

OUT

CN-

CN+

SE1

SE2

SE-

SH2

RTN

PE

DC Bus

Co

nt

ro

l

Po

w

er

Communic

ation

Advertising