Chapter 5

Connecting the Kinetix 6000M System

In this configuration, the 8-axis Bulletin 2094 power rail has four drive modules
and four IPIM modules. Each IPIM module is connected to four IDM units.
There are five sercos rings and each ring has its own 1756-M08SE sercos module
in the ControlLogix controller chassis.

Figure 28 - Kinetix 6000M Network Cable Example - IPIM Module to IDM Units (5 sercos rings)

IMPORTANT

It is not required that all Kinetix 6000 drives be on the same sercos ring;
however, it is required that all IDM units be on the same sercos ring as the
IPIM module they are connected to.

SERCOS interface

TM

Tx (rear)

Rx (front)

OK

CP

SERCOS interface

TM

Tx (rear)

Rx (front)

OK

CP

SERCOS interface

TM

Tx (rear)

Rx (front)

OK

CP

SERCOS interface

TM

Tx (rear)

Rx (front)

OK

CP

SERCOS interface

TM

Tx (rear)

Rx (front)

OK

CP

1756-M08SE Sercos

Interface Modules

Sercos Fiber-optic Ring 1

Logix Platform
(ControlLogix controller is shown)

2094-BCxx-Mxx-x

(400V-class) IAM Module

Bulletin 2090
Power/Brake Cables

Bulletin 2090
Feedback Cables

Bulletin 2090
Network Cables

Bulletin 2090

Hybrid Cables

Bulletin 2090

Network Cables

IDM System 1

IDM System 2

2094-BMxx-x

AM Modules

Compatible 400V-class

Rotary /Linear Motors or Actuators

(Bulletin MPL motors are shown)

Sercos Fiber-optic Ring 2

Sercos Fiber-optic Ring 3

Sercos Fiber-optic Ring 4

Sercos Fiber-optic Ring 5

Bulletin 2090
Network Cables

2094-SEPM-B24-S

IPIM Modules

Bulletin 2090
Hybrid Cables

Bulletin 2090
Hybrid Cables

Bulletin 2090
Hybrid Cables

Bulletin 2090
Hybrid Cables

IDM System 3

IDM System 4

2090-CTHP8, 2090-CTSRP

terminators required on last IDM

unit.