Minimum clearance requirements, Table 7, Table 8 – Rockwell Automation MDF-SB1304F Kinetix 6000M Integrated Drive-Motor System User Manual

Page 25

Advertising
background image

Rockwell Automation Publication 2094-UM003A-EN-P - May 2012

25

Planning the Kinetix 6000M System Installation

Chapter 2

Table 7 - Power Dissipation Specifications - Percent of DC Bus Current

Table 8 - Power Dissipation Specifications - Percent of IPIM Module Control Power

Minimum Clearance Requirements

This section provides information to assist you in sizing your cabinet and
positioning your IDM unit.

Figure 7

illustrates minimum clearance requirements for proper airflow and

installation:

Additional clearance is required for the cables and wires connected to the

top and front of the module.

Additional clearance left and right of the power rail is required when the

module is mounted adjacent to noise sensitive equipment or clean
wireways.

Table 9 - Minimum Cabinet Depth

Power Dissipation as % of DC Bus Current Output Rating

Watts

Heat Dissipation Formula

(1)

(1) x is percent of DC bus current output rating: any value between 0.0 and 1.0.

20%

40%

60%

80%

100%

2

7

14

25

38

Y = 33.95x

2

+ 3.18x

Control Power Input

Power Dissipation as % of IPIM Module Control

Power Output Rating

Watts

Heat Dissipation Formulas

(1)

(1) x is percent of IPIM module control power output rating: any value between 0.0 and 1.0.

Frequency
Hz

Voltage
AC

20%

40%

60%

80%

100%

50

120V

22

29

38

48

61

Y = 23.76x

2

+ 20.73x + 16.54

240V

34

42

52

63

76

Y = 18.56x

2

+ 30.19x + 27.41

60

120V

23

27

32

39

46

Y = 14.57x

2

+ 11.40x + 20.01

240V

38

49

62

76

92

Y = 19.63x

2

+ 43.22x + 28.75

Cat. No.

Cabinet Depth, Min

2094-SEPM-B24-S

272 mm (10.7 in.)