5 configure process display web page – Rockwell Automation MD65 EtherNet/IP Communication Module User Manual

Page 113

Advertising
background image

Viewing the Module’s Web Pages

10-11

10.2.5 Configure Process Display Web Page

The Configure Process Display web page enables you to set a
host’s parameters whose values you want shown in “Process
status” fields on the Home page and the Process Display pop-up
window. (When the module is operated in Multi-Drive mode, the
Home Page does not show a “Process status” field for a host.) By
default, this configuration is not protected. After configuration, the
settings can be protected by setting Web Features (parameter 30)
Proc Dsp Cfg Bit 1 value to “0” (Disabled). To change a protected
configuration, it must first be unprotected by setting the Proc Dsp
Cfg Bit 1 value back to “1” (Enabled).

Step 1.

To set a host’s parameters whose values you want shown
on Lines 1, 2, and 3 of the “Process status” fields in both
the Home Page (only Single mode) and Process Display
pop-up window, type the corresponding parameter
number in each box.

Step 2.

Click Save Changes.

Information

Description

Line 1 - parameter #

Number of parameter whose value you
want on Line 1.

Line 2 - parameter #

Number of parameter whose value you
want on Line 2.

Line 3 - parameter #

Number of parameter whose value you
want on Line 3.