EtherNet/IP Communications Module

Formulas for Converting

Display Value = ((Internal Value + Offset) x Multiplier x Base) / (Divisor x 10

Decimal Places

)

Internal Value =

((

Display Value x Divisor x 10

Decimal Place)

/

(Multiplier x Base))

-

Offset

Common Services

Object Specific Services

The table below lists the parameters for the
Get_Attributes_Scattered and Set_Attibutes_Scattered object-
specific service:

Important: The STRUCT may repeat up to 64 times in a

single message.

Service

Code

Implemented for:

Service Name

Class

Instance

0x0E

Yes

Yes

Get_Attribute_Single

0x10

Yes

Yes

Set_Attribute_Single

Service Code

Service Name

0x32

Get_Attributes_Scattered

1

1

The instance and attribute are ignored for these services.

0x34

Set_Attributes_Scattered

1

Name

Data Type

Description

Scattered Parameters STRUCT of

-

Parameter Number

WORD

Parameter to read or write

Parameter Value

WORD

Parameter value to read or write
(zero when reading)