Rockwell Automation MD65 EtherNet/IP Communication Module User Manual
Page 154

C-26
EtherNet/IP Communications Module
Formulas for Converting
Display Value = ((Internal Value + Offset) x Multiplier x Base) / (Divisor x 10
Decimal Places
)
Internal Value =
((
Display Value x Divisor x 10
Decimal Place)
/
(Multiplier x Base))
-
Offset
Common Services
Object Specific Services
The table below lists the parameters for the
Get_Attributes_Scattered and Set_Attibutes_Scattered object-
specific service:
Important: The STRUCT may repeat up to 64 times in a
single message.
Service
Code
Implemented for:
Service Name
Class
Instance
0x0E
Yes
Yes
Get_Attribute_Single
0x10
Yes
Yes
Set_Attribute_Single
Service Code
Service Name
0x32
Get_Attributes_Scattered
1
1
The instance and attribute are ignored for these services.
0x34
Set_Attributes_Scattered
1
Name
Data Type
Description
Scattered Parameters STRUCT of
-
Parameter Number
WORD
Parameter to read or write
Parameter Value
WORD
Parameter value to read or write
(zero when reading)