EtherNet I/P Objects
C-23
Instance Attributes
7
Get
Class
Revision
WORD
2 = MDI
8
Get
First
Parameter
Processing
Error
WORD
The first parameter that has been written
with a value outside of its range. A “0”
indicates no errors.
9
Set
Link
Command
BYTE
0 = No operation
1 = Clear all parameter links (This does not
clear links to function blocks.)
Attribute
ID
Access
Rule
Name
Data Type
Description
Attribute
ID
Access
Rule
Name
Data Type
Description
7
Get
MDI
Online
Read Full
STRUCT of
BOOL[32]
CONTAINER
1
CONTAINER
CONTAINER
CONTAINER
WORD
WORD
STRING[4]
UINT
UINT
UINT
INT
BYTE[3]
BYTE
STRING[16]
Descriptor
Parameter value
Minimum value
Maximum value
Default value
Next parameter
Previous parameter
Units (e.g., amp, Hz)
Multiplier
2
Divisor
2
Base
2
Offset
2
Link (source of the value) (0 = no link)
Always zero (0)
Parameter name
8
Get
MDI
Descriptor
BOOL[32]
Descriptor
9
Get/Set MDI
Parameter
Value
Various
Parameter value in NVS
3
10
Get/Set MDI RAM
Parameter
Value
Various
Parameter value in temporary
memory
11
Get/Set MDI Link
BYTE[3]
Link (parameter or function block that
is the source of the value) (0 = no link)
12
Get
Help
Object
Instance
WORD
ID for help text for this parameter