Rockwell Automation MD65 EtherNet/IP Communication Module User Manual

Page 93

Advertising
background image

Troubleshooting the Module and Network

9-5

9.1.4 NET B Status Indicator

Table 9.4 – NET B Status Indicator: State Definitions

Status

Cause

Corrective Action

Off

The module is not
powered or is not
transmitting on the
EtherNet/IP
network.

If Net A is off:

Securely connect the module to
the drive using the Internal
Interface cable and to the
network using an Ethernet
cable.

Correctly connect the Ethernet
cable to the Ethernet connector.

Set a unique IP address using a
BOOTP server or by disabling
BOOTP and using parameters.

If Net A is solid Red:

Configure the module to use a
unique IP address and cycle
power.

If Net A is flashing red:

Check the IP address in the
module and scanner.

Ping the module.

Normal condition if the module is
idle.

Flashing
Green

The module is
transmitting on the
EtherNet/IP
network.

No action required.