Configuring the RS-485 Network

Table 8.2 shows the parameters that must be set in the daisy-
chained drives.

Note: The RS-485 network is fixed at 19.2K baud, 8 data bits, no
parity, and 1 stop bit.

Important:Parameter A105 (Comm Loss Action) in the daisy-

chained drives is still used in Multi-Drive mode. If the
RS-485 cable is disconnected or broken, the
disconnected drive(s) will immediately take the
corresponding Comm Loss Action(s). On the EtherNet/
IP side, parameters 18 (Comm Flt Action) and 19 (Idle
Flt Action) in the MDCOMM-ENET determine the action
taken for ALL of the drives on the Multi-Drive node.

Table 8.3 shows the Multi-Drive parameters that must be set in the
MDCOMM-ENET.

After setting the MDCOMM-ENET parameters, set the Operating
Mode Switch (SW1) from Single drive operation to Multi-Drive
operation (set to ON position), and reset the module or cycle power.

Table 8.2 – Parameters for daisy-chained drives

Parameter

Value

P36 (Start Source)

5 (Comm Port)

P38 (Speed Reference)

5 (Comm Port)

A103 (Comm Data Rate)

4 (“19.2K”)

A104 (Comm Node Addr)

1-247 (must be unique)

A107 (Comm Format)

0 (“RTU 8-N-1”)

Table 8.3 – Parameters for MDCOMM-ENET

Parameter

Value

22 (MDI I/O Cfg)

0 = Drive 0 connected
1 = Drives 0-1 connected
2 = Drives 0-2 connected
3 = Drives 0-3 connected
4 = Drives 0-4 connected

24 (Drv 0 Addr)

= Parameter A104 (Comm Node Address) in Drive 0

25 (Drv 1 Addr)

= Parameter A104 (Comm Node Address) in Drive 1

26 (Drv 2 Addr)

= Parameter A104 (Comm Node Address) in Drive 2

27 (Drv 3 Addr)

= Parameter A104 (Comm Node Address) in Drive 3

28 (Drv 4 Addr)

= Parameter A104 (Comm Node Address) in Drive 4