Rockwell Automation MD65 EtherNet/IP Communication Module User Manual

Page 144

Advertising
background image

C-16

EtherNet/IP Communications Module

N-Files

MDI Port Assignments

MDI Port No.

Single-Drive Mode

Multi-Drive Mode

0

The drive

Drive 0

1

The module

Drive 1

2

The slave

Drive 2

3

Not supported

Drive 3

4

Not supported

Drive 4

5

Not supported

The module

N-File

Description

N40

This N-file lets you use Emulated Block Transfer messages to read and write
many types of MDI messages. To use Emulated Block Transfer messages, you
send a Write message to N40:0 – N40:63, wait until the module responds with a
reply message, and then read the response data in N40:0 – N40:63 with a Read
message.

Bits 15 to 8 are the Most Significant Byte. Bits 7 to 0 are the Least Significant
Byte.

Write

Read

Bits

15

0 15

0

N40:0

0x00

Length (in Bytes)

0x00

Length (in Bytes)

N40:1

MDI Port

1

0x81

Status Size

Status Type

N40:2

0x00

CIP Services

Data
(length varies based on message)

N40:3

CIP Class

N40:4

CIP Instance

N40:5

CIP Attribute

N40:6

Data
(length varies based on message)

…

N40:63

1

See MDI Port Assignments listed on page C-16.

N41

This N-file lets you read and write control I/O messages. You can write control I/O
messages only when all of the following conditions are true:

•

The module is not receiving I/O from a scanner. For example, there is no

scanner on the network, the scanner is in idle (program) mode, the scanner
is faulted, or the module is not mapped to the scanner.

•

The value of N42:3 is set to a non-zero value.

Write

Read

N41:0
N41:1
N41:2

Logic Command Word
Unused
Reference

Logic Status Word
Unused
Feedback