Rockwell Automation MD65 EtherNet/IP Communication Module User Manual

Page 91

Advertising
background image

Troubleshooting the Module and Network

9-3

9.1.2 MS Status Indicator

Table 9.2 – MS Status Indicator: State Definitions

Status

Cause

Corrective Action

Off

The module is not
powered or properly
connected to the
drive.

•

Securely connect the module
to the MD65 drive using the
Internal Interface cable.

•

Apply power to the drive and
network.

Flashing
Red

The module has
failed the firmware
test.

•

Cycle power to the drive.

•

If cycling power does not
correct the problem, the
parameter settings may have
been corrupted. Reset defaults
and reconfigure the module.

•

If resetting defaults does not
correct the problem, flash the
module with the latest firmware
release.

Solid
Red

The module has
failed the hardware
test.

•

Cycle power to the drive.

•

Replace the module.

Flashing
Green

The module is
operational but is not
transferring I/O data.

•

Place the scanner in RUN
mode.

•

Program the controller to
recognize and transmit I/O to
the module.

•

Configure the module for the
program in the controller.

Solid
Green

The module is
operational and
transferring I/O data.

•

No action required.