Using Multi-Drive Mode

8-7

Important:

MDCOMM-ENET parameters can be set using MDI
peripheral (OIM) ONLY when the Operating Mode
Switch is in the Single

8.5

Example Multi-Drive Ladder Logic
Program

The ladder logic program example demonstrates using Multi-Drive
mode with five drives. See figure 8.2 for a system layout diagram.

8.5.1 Function of Example Program

The example program provided is for the ControlLogix, but other
controllers can also be used. This example program enables you to:

View status information from the drives such as Ready, Fault, At
Speed, and Feedback.

Control the drives using various Logic Command bits (Stop, Start,
etc.) and Reference.

Perform a single parameter read and write for each drive. The
example uses drive parameter 39 (Accel Time) for both so you
can see (read) the change after a write is performed.

8.5.2 Module Settings for the Example Program

The Operating Mode Switch (SW1) on the module is set to the
Multi-Drive operation position. Table 8.4 shows the module
parameter settings.

Table 8.4 – Module Parameter Settings

Parameter

Value

Description

22 (MDI I/O Cfg)

4

“Drives 0-4” - 5 drives on 1 node

24 (Drv 0 Addr)

1

1

The settings for these parameters must match the Parameter A104
(Comm Node Addr) settings in the respective drives.

1

Modbus address of Drive 0

25 (Drv 1 Addr)

1

2

Modbus address of Drive 1

26 (Drv 2 Addr)

1

3

Modbus address of Drive 2

27 (Drv 3 Addr)

1

4

Modbus address of Drive 3

28 (Drv 4 Addr)

1

5

Modbus address of Drive 4