Rockwell Automation MD65 EtherNet/IP Communication Module User Manual

Page 18

Advertising
background image

3-2

EtherNet/IP Communications Module

Step 1.

Set the Operating Mode Switch (SWI) for Single or Multi-
Drive operation (see figure 3.1 and setting descriptions
below). For complete details on Multi-Drive operation, see
chapter 8.

Step 2.

Set the Web Pages Switch (SW2) to enable or disable the
module web pages. By default, the module web pages are
enabled. For complete details on the module web pages,
see chapter 10.

Figure 3.1 – Setting Single/Multi-Drive Operation and Web Page Enable

Switches

1

OPERATING

MODE SWITCH

Single-Drive

Operation

Position

Multi-Drive

Operation

Position

Disable Web
Position

Enable Web
Position

WEB PAGES
SWITCH

2

Table 3.1 – Setting 1 Descriptions

SW1 Setting

Description

Down position

(DN = Closed = 0)

Sets the module for Single drive mode
(default setting) using a single drive
connection.

Important:

In this mode, connections to
multiple drives must be
removed since all powered
and connected hosts will
respond to any message sent
by the module.

Up position

(UP = Open = 1)

Sets the module for Multi-Drive operation
mode using up to 5 different drives. MDI
peripherals do not operate with the module
in this mode.