Rockwell Automation MD65 EtherNet/IP Communication Module User Manual

Page 92

Advertising
background image

9-4

EtherNet/IP Communications Module

9.1.3 NET A Status Indicator

Table 9.3 – NET A Status Indicator: State Definitions

Status

Cause

Corrective Action

Off

The module and/or
network is not
powered, the
module is not
connected properly
to the network, or
the module needs
an IP address.

•

Securely connect the module to
the drive using the Internal
Interface (ribbon) cable and to
the network using an Ethernet
cable.

•

Correctly connect the Ethernet
cable to the Ethernet connector.

•

Set a unique IP address using a
BOOTP server or disabling
BOOTP and using parameters.

•

Apply power to the drive and
network.

Solid Red

The device has
detected an error
and is incapable of
communicating on
the network.

•

Replace the module.

Flashing
Red

An EtherNet/IP
connection has
timed out.

•

Place the scanner in RUN
mode.

•

Check the amount of traffic on
the network.

Flashing
Red/
Green

The module is
performing a self
test.

•

No action is required.

Flashing
Green

The module is
properly connected
but is not
communicating
with any devices
on the network.

•

Place the controller in RUN
mode.

•

Program a controller or peer
device to recognize and
transmit I/O or make a
messaging connection to the
module.

•

Configure the module for the
program in the controller.

Solid
Green

The module is
properly connected
and
communicating
with the network.

•

No action required.