9-4

EtherNet/IP Communications Module

9.1.3 NET A Status Indicator

Table 9.3 – NET A Status Indicator: State Definitions

Status

Cause

Corrective Action

Off

The module and/or
network is not
powered, the
module is not
connected properly
to the network, or
the module needs
an IP address.

Securely connect the module to
the drive using the Internal
Interface (ribbon) cable and to
the network using an Ethernet
cable.

Correctly connect the Ethernet
cable to the Ethernet connector.

Set a unique IP address using a
BOOTP server or disabling
BOOTP and using parameters.

Apply power to the drive and
network.

Solid Red

The device has
detected an error
and is incapable of
communicating on
the network.

Replace the module.

Flashing
Red

An EtherNet/IP
connection has
timed out.

Place the scanner in RUN
mode.

Check the amount of traffic on
the network.

Flashing
Red/
Green

The module is
performing a self
test.

No action is required.

Flashing
Green

The module is
properly connected
but is not
communicating
with any devices
on the network.

Place the controller in RUN
mode.

Program a controller or peer
device to recognize and
transmit I/O or make a
messaging connection to the
module.

Configure the module for the
program in the controller.

Solid
Green

The module is
properly connected
and
communicating
with the network.

No action required.