Configuring the EtherNet/IP Module

4-11

4.7.2 Resetting the Module

Changes to some module parameters require that you reset the
module before the new settings take effect. You can reset the
module by cycling power to the drive or by using module parameter
17 (Reset Module).

Set parameter 17 (Reset Module) to “Reset Module.” See figure
4.11.

When you enter 1 (Reset Module), the module will be immediately
reset. When you enter 2 (Set Defaults), the module will set all
module parameters to their factory-default settings. The module
should be reset after performing a “Set Defaults.”

The value of this parameter will be restored to 0 (Ready) after the
module is reset or after resetting the defaults.

!

ATTENTION: If the module is transmitting control
I/O to the drive, the drive may fault when you reset
the module. Determine how your drive will respond
before resetting a connected module. Failure to
observe this precaution could result in bodily injury
or damage to equipment.

Figure 4.11 – Reset Screen on an LCD OIM

Port 5 Device

MDCOMM-ENET

Parameter #:17
Reset Module

1

Reset Module

Value

Description

0

Ready (default)

1

Reset Module

2

Set Defaults