B-8

EtherNet/IP Communications Module

Displays the Drives that are active in the Multi-Drive mode.

.

Sets the corresponding node addresses of the daisy-chained drives
when the module Operating Mode Switch (SW1) is set for
Multi-Drive operation.

Important: The settings for these parameters must match the

Comm Node Addr parameter settings in the respective
drives. Each setting must also be unique (no duplicate
node address).

23

MDI I/O Act

Range:

0 = Drive Active
1 = Drive Inactive

Default:

xxx0 0000

Type:

Read Only

Reset Required: N/A

0

0

0

0

0

x x

x

0

1

2

3

4

5

7 6

0 = Drive 0 Active
1 = Drive 1 Active
2 = Drive 2 Active
3 = Drive 3 Active
4 = Drive 4 Active
5 = Not Used
6 = Not Used
7 = Not Used

24
25
26
27
28

Drv 0 Addr
Drv 1 Addr
Drv 2 Addr
Drv 3 Addr
Drv 4 Addr

Range:

1 - 247

Default:

Drv 0 Addr = 100
Drv 1 Addr = 101
Drv 2 Addr = 102
Drv 3 Addr = 103
Drv 4 Addr = 104

Type:

Read/Write

Reset Required: Yes