6-2

EtherNet/IP Communications Module

6.2

Understanding the I/O Image

The terms input and output are defined from the scanner’s point of
view. Therefore, Output I/O is data that is output from the scanner
and consumed by the EtherNet/IP module. Input I/O is status data
that is produced by the module and consumed as input by the
scanner. The I/O image table will vary based on the following:

Configuration of the Operating Mode Switch (SW1) on the
module and parameter 22 (MDI I/O Cfg). The image table always
uses consecutive words starting at word 0.

Figure 6.1 illustrates an example of a Single drive I/O image (16-bit
words).

Single mode is the typical configuration, where one node consists of
a MD65 drive with a MDCOMM-ENET.

For Multi-Drive mode, where one node can consist of up to 5 drives,
refer to chapter 8.

6.3

Using Logic Command/Status

When enabled, the Logic Command/Status word is always word 0
in the I/O image. The Logic Command is a 16-bit word of control
produced by the scanner and consumed by the module. The Logic
Status
is a 16-bit word of status produced by the module and
consumed by the scanner.

Figure 6.1 – Single Drive Example of I/O Image

Controller

Scanner

Adapter

Word and I/O

EtherNet/IP

Output
Image
(Write)

Input
Image
(Read)

Message

Handler

Message

Buffer

0 Logic Status
1 Feedback

Logic Status
Feedback

Message

Handler

0 Logic Command
1 Reference

Logic Command
Reference

MDI

MD65 Drive