Rockwell Automation MD65 EtherNet/IP Communication Module User Manual
Page 120
B-2
EtherNet/IP Communications Module
Display the Single or Multi-Drive operating mode selected with the
Operating Mode Switch (SW1) on the module.
Configures the module to use BOOTP so that you can set its IP
address, subnet mask, and gateway address with a BOOTP server.
Sets the bytes in the IP address.
Important: To set the IP address using these parameters,
parameter 02 (BOOTP) must be set to Disabled.
01
Mode
Range:
0 = Single Drive
1 = Multiple Drive
Default:
0 = Single Drive
Type:
Read Only
Reset Required: N/A
02
BOOTP
Range:
0 = Disabled
1 = Enabled
Default:
1 = Enabled
Type:
Read/Write
Reset Required: Yes
3
4
5
6
IP Addr Cfg 1
IP Addr Cfg 2
IP Addr Cfg 3
IP Addr Cfg 4
Range:
0 to 255
Default:
0
Type:
Read/Write
Reset Required: Yes
255 . 255 . 255 . 255
IP Addr Cfg 1
IP Addr Cfg 2
IP Addr Cfg 3
IP Addr Cfg 4