B-2

EtherNet/IP Communications Module

Display the Single or Multi-Drive operating mode selected with the
Operating Mode Switch (SW1) on the module.

Configures the module to use BOOTP so that you can set its IP
address, subnet mask, and gateway address with a BOOTP server.

Sets the bytes in the IP address.

Important: To set the IP address using these parameters,

parameter 02 (BOOTP) must be set to Disabled.

01

Mode

Range:

0 = Single Drive
1 = Multiple Drive

Default:

0 = Single Drive

Type:

Read Only

Reset Required: N/A

02

BOOTP

Range:

0 = Disabled
1 = Enabled

Default:

1 = Enabled

Type:

Read/Write

Reset Required: Yes

3
4
5
6

IP Addr Cfg 1
IP Addr Cfg 2
IP Addr Cfg 3
IP Addr Cfg 4

Range:

0 to 255

Default:

0

Type:

Read/Write

Reset Required: Yes

255 . 255 . 255 . 255

IP Addr Cfg 1

IP Addr Cfg 2

IP Addr Cfg 3

IP Addr Cfg 4