9.1.1 DRIVE Status Indicator

Table 9.1 – DRIVE Status Indicator: State Definitions

Status

Cause

Corrective Action

Off

The module is not
powered or is not
connected properly to
the drive.

Securely connect the module
to the drive using the Internal
Interface (ribbon) cable.

Apply power to the drive.

Flashing
Red

In Single mode, the
module is not receiving
communication from
the drive.

In Multi-Drive mode, the
module is not receiving
communication from
the drive, or the drive is
not a Reliance Electric
drive.

Verify the setting for
parameter 22 (MDI I/O Cfg).

Verify that cables are
securely connected and not
damaged. Replace cables if
necessary.

Cycle power to the drive.

Use Reliance Electric MD65
and MD 60 AC Drives.

Solid
Red

The drive has refused
an I/O connection from
the module.

Another MDI peripheral
is using the same MDI
port as the module.

Important: Cycle power to the
product after making any of the
following corrections:

Verify that all MDI cables are
securely connected and not
damaged. Replace cables if
necessary.

Orange

In Single mode, the
drive is not a Reliance
Electric drive.

Use a Reliance Electric
MD65 AC Drive.

Flashing
Green

The module is
establishing
communications with
the drive.

No action required. This
status indicator will turn solid
green or flash red.

Solid
Green

The module is properly
connected and is
communicating with the
drive.

No action required.