1 setting the fault configuration parameters – Rockwell Automation MD65 EtherNet/IP Communication Module User Manual

Page 32

Advertising
background image

4-10

EtherNet/IP Communications Module

Changes to these parameters take effect immediately. A reset is not
required.

4.7.1 Setting the Fault Configuration Parameters

If you set parameter 18 (Comm Flt Action) or parameter 19 (Idle Flt
Action) to “Send Flt Cfg,” the values in the parameters shown in
table 4.5 are sent to the drive after a communications fault and/or
idle fault occurs. You must set these parameters to values required
by your application.

Changes to these parameters take effect immediately. A reset is not
required.

Table 4.4 – Selections for Drive Response to Communication Fault

Value

Action

Description

0

Fault (default)

The drive is faulted and stopped (Default).

1

Stop

The drive is stopped, but not faulted.

2

Zero Data

The drive is sent 0 for output data after a
communications disruption. This does not
command a stop.

3

Hold Last

The drive continues in its present state after a
communications disruption.

4

Send Flt Cfg

The drive is sent the data that you set in the
fault configuration parameters, Flt Cfg Logic
(20) and Flt Cfg Ref (21).

Figure 4.10 – Comm Flt Action Screen and Idle Flt Action Screen on an LCD

OIM

Port 5 Device

MDCOMM-ENET

Parameter #: 18
Comm Flt Action

0

Fault

Port 5 Device

MDCOMM-ENET

Parameter #: 19
Idle Flt Action

0

Fault

Table 4.5 – Fault Configuration Parameters

Parameter Number

Name

Description

20

Flt Cfg Logic

A 16-bit value sent to the drive
for Logic Command.

21

Flt Cfg Ref

A 16-bit value (0 - 65535) sent
to the drive as a Reference.