Rockwell Automation MD65 EtherNet/IP Communication Module User Manual

Page 143

Advertising
background image

EtherNet I/P Objects

C-15

Message Structure for Execute_DH+

The module supports the following PCCC command types:

Request

Response

Name

Data

Type

Description

Name

Data

Type

Description

DLink

UINT

Destination Link ID

DLink

UINT

Destination Link ID

DSta

USINT

Destination Station
Number

DSta

USINT

Destination Station
Number

DUser

USINT

Destination “User”
number

DUser UDINT

Destination

“User”

number

SLink

UINT

Source Link ID

SLink

Product
Specific

Source Link ID

SSta

USINT

Source Station
number

SSta

USINT

Source Station
number

SUser

USINT

Source User number

SUser

USINT

Source User number

CMD

USINT

Command Byte

CMD

USINT

Command Byte

STS

USINT

0

STS

USINT

Status byte

TNSW

UINT

Transport word

TNSW

UINT

Transport word. Same
value as the request.

FNC

USINT

Function code. Not
used for all CMD’s.

EXT_STS USINT

Extended status. Not
used for all CMD’s.

PCCC_
params

ARRAY
of USINT

CMD/FNC specific
parameters

PCCC_
results

ARRAY
of USINT

CMD/FNC specific
result data

CMD

FNC

Description

0x06

0x03

Identify host and some status

0x0F

0x67

PLC-5 Typed write

0x0F

0x68

PLC-5 Typed read

0x0F

0x95

Encapsulate other protocol

0x0F

0xA2

SLC 500 protected typed read with 3 address fields

0x0F

0xAA

SLC 500 protected typed write with 3 address fields

0x0F

0xA1

SLC 500 protected typed read with 2 address fields

0x0F

0xA9

SLC 500 protected typed write with 3 address fields

0x0F

0x00

Word range read

0x0F

0x01

Word range write

Advertising