Using Multi-Drive Mode

8-9

Table 8.7 describes the tags used for Drive 0.

The same type of Tags are also used for Drive 1 through Drive 4.

Table 8.7 – Common Tags for ControlLogix Example

Tag Name

Type

Description

Drive 0 Command Stop

BOOL

Logic Command bit 0 (STOP)

Drive 0 Command Start

BOOL

Logic Command bit 1

(START)

Drive 0 Command Jog

BOOL

Logic Command bit 2 (JOG)

Drive 0 Command Clear
Faults

BOOL

Logic Command bit 3

(CLEAR FAULTS)

Drive 0 Command Forward

BOOL

Logic Command bit 4

(FORWARD)

Drive 0 Reference

INT

Speed Reference

Drive 0 Status Ready

BOOL

Logic Status bit 0 (READY)

Drive 0 Status Active

BOOL

Logic Status bit 0 (ACTIVE)

Drive 0 Status Forward

BOOL

Logic Status bit 0

(FORWARD)

Drive 0 Status Faulted

BOOL

Logic Status bit 0 (FAULT)

Drive 0 Status at
Reference

BOOL

Logic Status bit 0

(AT SPEED)

Drive 0 Feedback

INT

Speed Reference

Perform Parameter Read 0

BOOL

Initiates the parameter read

Parameter RD Value 0

INT

Read value of the parameter

Parameter RD Message 0

MESSAGE

Get_Attribute_Single (Read)

Perform Parameter Write 0

BOOL

Initiates the parameter value

Parameter WR Value 0

INT

Write value to the parameter

Parameter WR Message 0

MESSAGE

Set_Attribute_Single (Write)