6-6

EtherNet/IP Communications Module

6.8

Sample ControlLogix Ladder Logic
Program

Figure 6.5 – Sample ControlLogix Ladder Logic Program for I/O Messaging

ControlLogix to

The ControlLogix system consists of a 1756-ENBT in slot 5 communicating over Ethernet with a MD65 drive/ MDCOMM-

ENET EtherNet/IP module.

The I/O image is as follows:

INPUT (4 INT words) OUTPUT (2 INT words)

MD65-Demo:I.Data[0] = ENBT Overhead MD65-Demo:I.Data[0] = MD65 Logic Command

MD65-Demo:I.Data[1] = ENBT Overhead MD65-Demo:I.Data[1] = MD65 Reference

MD65-Demo:I.Data[2] = MD65 Logic Status

MD65-Demo:I.Data[3] = MD65 Feedback

Logic Status information rungs are provided for display purposes only. The MD65_Demo: I.Data[2].x.bits could be used

directly elsewhere in the ladder program.

0

MD65 Demo

Logic Status

READY

MD65_Demo:I.Data[2].0

MD65

READY

Drive_Ready

ControlLogix to MD65 on EtherNet/IP Demo

The ControlLogix system consists of a 1756-ENBT in slot 5 communicating over Ethernet with

The I/O image is as follows:

INPUT (4 INT words) OUTPUT (2 INT words)

Logic Status information rungs are provided for display purposes only. T

directly elsewhere in the ladder program.

1

MD65 Demo

Logic Status

ACTIVE

MD65_Demo:I.Data[2].1

MD65

ACTIVE

Drive_Active

2

MD65 Demo

Logic Status

ACTUAL

DIRECTION

MD65_Demo:I.Data[2].2

MD65

FORWARD

Drive_Forward

3

/

MD65 Demo

Logic Status

ACTUAL

DIRECTION

MD65_Demo:I.Data[2].2

MD65

REVERSE

Drive_Reverse

4

MD65 Demo

Logic Status

FAULT

MD65_Demo:I.Data[2].7

MD65

FAULT

Drive_Fault

5

MD65 Demo

Logic Status

AT SPEED

MD65_Demo:I.Data[2].8

MD65

AT SPEED

Drive_At_Speed