Rockwell Automation MD65 EtherNet/IP Communication Module User Manual

Page 42

Advertising
background image

5-6

EtherNet/IP Communications Module

Step 3.

Edit the fields listed in table 5.2.

Step 4.

Under Connection Parameters, edit the fields listed in
table 5.3.

Type the number of bytes that are required for your I/O in
the Input Size and Output Size boxes. The size will depend
on the I/O that you enabled in the module.This information
can be found in parameter 22 (MDI I/O Cfg) in the module.
Table 5.4 shows common configuration Input/Output sizes.

Figure 5.8 – Module Properties Dialog Box - Page 1

Reliance Electric

MD65_Demo

Table 5.2 – Edit Module Properties

Field

Enter This Information

Name

A name to identify the module and drive.

Comm. Format Data - INT.

This setting formats the data in 16-bit words.

IP Address

The IP address of the module.

Table 5.3 – Edit Connection Parameters

Field

Assembly

Instance Size

Input

1 (This value is
required.)

The value will vary based on your
application (setting of parameter
22 (MDI I/O Config). It will contain
2 additional words for ENBT
overhead. Refer to table 5.4.

Output

2 (This value is
required.)

The value will vary based on your
application (setting of Parameter
22 (MDI I/O Config).

Configuration

6 (This value is
required.)

0 (This value is required.)