Rockwell Automation RECOMM-ENET EtherNet/IP Communications Module User Manual

Page 126

Advertising
background image

B-8

EtherNet/IP Communications Module

Displays the I/O that the module is actively transmitting. The value
of this parameter will usually be equal to the value of DPI I/O Cfg
(23).

Sets the Logic Command data that is sent to the drive if the
following is true:

• Comm Flt Action (21) is set to Send Flt Cfg and communications

are disrupted.

• Idle Flt Action (22) is set to Send Flt Cfg and the scanner is put

into Program or Test mode.

• Peer Flt Action (41) is set to Send Flt Cfg and communications

are disrupted.

Important: The bit definitions will depend on the product to which

the module is connected. If the drive uses a 16-bit
Reference, the most significant word of this value must
be set to zero (0) or a fault will occur.

24

DPI I/O Active

Range:

See figure B.2.

Default:

xxx0 0001

Type:

Read Only

Reset Required: N/A

Figure B.2 – DPI I/O Active (24)

0

0

0

1

0

x

x

x

0

1

2

3

4

5

6

7

1 = I/O Enabled
0 = I/O Disabled
x =Not Used

Cmd/Ref

Datalink A

Datalink B

Datalink C

Datalink D

Not Used

Not Used

Not Used

25

Flt Cfg Logic

Range:

0000 0000 0000 0000 to 1111 1111 1111 1111

Default:

0000 0000 0000 0000

Type:

Read/Write

Reset Required: No