Rockwell Automation RECOMM-ENET EtherNet/IP Communications Module User Manual
Page 126

B-8
EtherNet/IP Communications Module
Displays the I/O that the module is actively transmitting. The value
of this parameter will usually be equal to the value of DPI I/O Cfg
(23).
Sets the Logic Command data that is sent to the drive if the
following is true:
• Comm Flt Action (21) is set to Send Flt Cfg and communications
are disrupted.
• Idle Flt Action (22) is set to Send Flt Cfg and the scanner is put
into Program or Test mode.
• Peer Flt Action (41) is set to Send Flt Cfg and communications
are disrupted.
Important: The bit definitions will depend on the product to which
the module is connected. If the drive uses a 16-bit
Reference, the most significant word of this value must
be set to zero (0) or a fault will occur.
24
DPI I/O Active
Range:
See figure B.2.
Default:
xxx0 0001
Type:
Read Only
Reset Required: N/A
Figure B.2 – DPI I/O Active (24)
0
0
0
1
0
x
x
x
0
1
2
3
4
5
6
7
1 = I/O Enabled
0 = I/O Disabled
x =Not Used
Cmd/Ref
Datalink A
Datalink B
Datalink C
Datalink D
Not Used
Not Used
Not Used
25
Flt Cfg Logic
Range:
0000 0000 0000 0000 to 1111 1111 1111 1111
Default:
0000 0000 0000 0000
Type:
Read/Write
Reset Required: No