Rockwell Automation RECOMM-ENET EtherNet/IP Communications Module User Manual
Page 131

Module Parameters
B-13
Sets the bytes in the IP address that specifies the device from which
the module receives (consumes) Peer I/O data.
Important: Changes to these parameters are ignored when
parameter 47 (Peer Inp Enable) is On.
Sets the timeout for a peer connection. If the time is reached without
the module receiving (consuming) a message, the module will
respond with the action specified in parameter 41 (Peer Flt Action).
In a module receiving (consuming) Peer I/O, the value of this
parameter must be greater than the product of the value of
parameter 52 (Peer Out Time) in the module transmitting
(producing) Peer I/O multiplied by the value of parameter 53 (Peer
Out Skip) in the module transmitting (producing) Peer I/O.
42
43
44
45
Peer Inp Addr 1
Peer Inp Addr 2
Peer Inp Addr 3
Peer Inp Addr 4
Range:
0 to 255
Default:
0
Type:
Read/Write
Reset Required: No
255 . 255 . 255 . 255
Peer Inp Addr 1
Peer Inp Addr 2
Peer Inp Addr 3
Peer Inp Addr 4
46
Peer Inp Timeout
Range:
0.01 to 10.00 sec
Default:
10.00 sec
Type:
Read/Write
Reset Required: No