Configuring the EtherNet/IP Module
4-22
4.12 Viewing the Module Configuration
The parameters in table 4.5 provide information about how the
module is configured. You can view these parameters at any time.
Table 4.5 – Module Configuration Parameters
No
Name and Description
Details
17 EN Rate Act
The actual network data rate.
Values
0 = No Link
1 = 10 Mbps Full
2 = 10 Mbps Half
3 = 100 Mbps Full
4 = 100 Mbps Half
Type:
Read Only
18 Ref / Fdbk Size
Size of the Reference/Feedback. The drive
determines the size of the Reference/Feedback.
Values:
0 = 16-bit
1 = 32-bit
Type:
Read Only
19 Datalink Size
Size of each Datalink word. The drive determines
the size of Datalinks.
Values:
0 = 16-bit
1 = 32-bit
Type:
Read Only
24 DPI I/O Act
I/O that the module is actively transmitting. The
value of this parameter will usually be equal to the
value of parameter 23 (DPI I/O Config).
Bit Values:
0 = I/O disabled
1 = I/O enabled
Type:
Read Only
Bit Definitions
0 = Cmd/Ref
1 = Datalink A
2 = Datalink B
3 = Datalink C
4 = Datalink D
5 = Not Used
6 = Not Used
7 = Not Used
48 Peer Inp Status
Status of the consumed peer input connection.
Values:
0 = Off
1 = Waiting
2 = Running
3 = Faulted
Type:
Read Only
Bit
Default
1
0
0
0
0
x x
x
0
1
2
3
4
5
7 6