Rockwell Automation RECOMM-ENET EtherNet/IP Communications Module User Manual

Page 152

Advertising
background image

C-16

EtherNet/IP Communications Module

N201 – N212 These N-files let you read and write parameter values in DPI Peripherals (for

example, an OIM or module) as 32-bit double words. You can interpret the
data in various ways (for example, 32-bit real, 32-bit integer) To read a
parameter, you need to send a message with two elements. For example, to
read parameter 1 in the peripheral connected to DPI port 1, read two
elements beginning at N201:2. As another example, to read parameters 2 – 6
in the peripheral connected to DPI port 5 (the module), read ten elements
beginning at N209:4.

N201:0 – 1
N201:2 – 249
N202:0 – 249
N203:0 – 1
N203:2 – 249
N204:0 – 249
N205:0 – 1
N205:2 – 249
N206:0 – 249
N207:0 – 1
N207:2 – 249
N208:0 – 249
N209:0 – 1
N209:2 – 249
N210:0 – 249
N211:0 – 1
N211:2 – 249
N212:0 – 249

Number of parameters in the DPI peripheral at DPI port 1
Parameters 1 – 124 in the DPI peripheral at DPI port 1
Parameters 125 – 249 in the DPI peripheral at DPI port 1
Number of parameters in the DPI peripheral at DPI port 2
Parameters 1 – 124 in the DPI peripheral at DPI port 2
Parameters 125 – 249 in the DPI peripheral at DPI port 2
Number of parameters in the DPI peripheral at DPI port 3
Parameters 1 – 124 in the DPI peripheral at DPI port 3
Parameters 125 – 249 in the DPI peripheral at DPI port 3
Number of parameters in the DPI peripheral at DPI port 4
Parameters 1 – 124 in the DPI peripheral at DPI port 4
Parameters 125 – 249 in the DPI peripheral at DPI port 4
Number of parameters in the DPI peripheral at DPI port 5
Parameters 1 – 124 in the DPI peripheral at DPI port 5
Parameters 125 – 249 in the DPI peripheral at DPI port 5
Number of parameters in the DPI peripheral at DPI port 6
Parameters 1 – 124 in the DPI peripheral at DPI port 6
Parameters 125 – 249 in the DPI peripheral at DPI port 6

N-File

Description