Rockwell Automation RECOMM-ENET EtherNet/IP Communications Module User Manual

Page 44

Advertising
background image

4-18

EtherNet/IP Communications Module

!

ATTENTION: Parameter 41 (Peer Flt Action) lets
you determine the action of the module and
connected drive if the module times out

.

By default,

this parameter faults the drive if you have configured
the module for peer-to-peer communication. You can
set this parameter so that the drive continues to run.
Precautions should be taken to ensure that the
setting of this parameter does not create a hazard of
injury or equipment damage. When commissioning
the drive, verify that your system responds correctly
to various situations (for example, a disconnected
cable). Failure to observe this precaution could result
in bodily injury and/or damage to equipment.

Table 4.3 – Selections for Drive Response to Communication Fault

Value

Action

Description

0

Fault (default) The drive is faulted and stopped (Default).

1

Stop

The drive is stopped, but not faulted.

2

Zero Data

The drive is sent 0 for output data after a
communications disruption. This does not
command a stop.

3

Hold Last

The drive continues in its present state.

4

Send Flt Cfg

The drive is sent the data that you set in
the fault configuration parameters, Flt Cfg
Logic (25) through Flt Cfg D2 In (34).

Figure 4.26 – Comm Flt Action Screen and Idle Flt Action Screen on an LCD

OIM

Port 5 Device

RECOMM-ENET

Parameter #: 21
Comm Flt Action

0

Fault

Port 5 Device

RECOMM-ENET

Parameter #: 22
Idle Flt Action

0

Fault