Rockwell Automation RECOMM-ENET EtherNet/IP Communications Module User Manual
Page 93

Troubleshooting the Module and Network
8-3
8.1.2 MS Status Indicator
Table 8.3 – MS Status Indicator: State Definitions
Status
Cause
Corrective Action
Off
The module is not
powered.
•
Securely connect the module
to the drive using the Internal
Interface cable.
•
Apply power to the drive and
network.
Flashing
Red
The module has
failed the firmware
test.
The module is being
flash upgraded.
•
Clear faults in the module.
•
Cycle power to the drive.
•
If cycling power does not
correct the problem, the
parameter settings may have
been corrupted. Reset defaults
and reconfigure the module.
•
If resetting defaults does not
correct the problem, flash the
module with the latest firmware
release.
Solid
Red
The module has
failed the hardware
test.
•
Cycle power to the drive.
•
Replace the module.
Flashing
Green
The module is
operational but is not
transferring I/O data.
•
Place the scanner in RUN
mode.
•
Program the controller to
recognize and transmit I/O to
the module.
•
Configure the module for the
program in the controller.
•
Normal behavior if no DPI I/O
is enabled.
Solid
Green
The module is
operational and
transferring I/O data.
•
No action.